SANC02 Trace Heat FG2-6L
SANC02 Trace Heat FG2-6L is backordered and will ship as soon as it is back in stock.
FG2-6L Trace Heat Kit
The FG2-6L Trace Heat Kit is a 208–240V, single-phase electric heating cable designed for freeze protection of metal or plastic water pipes. The preassembled kit includes a 6-foot self-regulating heating cable and a 6-foot power cord.
In SANCO₂ installations, the kit provides freeze protection for exterior piping between the storage tank and heat pump. The insulated power cord has bare wire ends for connection to the power supply.
Key Features & Specifications
| Specification | Details |
|---|---|
| Model | FG2-6L |
| Product Type | Heat trace kit for pipe freeze protection |
| Electrical Supply | 208–240V, single-phase |
| Specified Circuit Breaker | 15A |
| Heating Cable Wire Gauge | 16 AWG |
| Heating Cable Length | 6 feet |
| Power Cord Length | 6 feet |
| Cable Construction | Self-regulating cable with protective tinned copper braid and an outer polyolefin jacket. |
| Pipe Compatibility | Metal or plastic water pipes |
| Certification | CSA — United States and Canada |
Temperature Limits & Physical Data
| Specification | Value |
|---|---|
| Maximum Exposure Temperature | 150°F |
| Minimum Installation Temperature | 5°F |
| Electrical Classification | Nonhazardous locations only |
| Chemical Exposure | None, as specified in the manufacturer submittal |
| Maximum Cable Width | 0.45 inch |
| Maximum Cable Thickness | 0.24 inch |
| Minimum Bend Radius | ⅝ inch |
Heating Performance
| Manufacturer Rating | Value |
|---|---|
| Minimum Output on Pipe at 40°F | 30 W |
| Minimum Output on Pipe at 5°F | 46 W |
| Maximum Current Draw on Pipe at 40°F | 0.21 A |
| Maximum Current Draw on Pipe at 5°F | 0.32 A |
Control & Installation
Heating output self-regulates with pipe temperature: output per foot decreases as the pipe becomes warmer. Self-regulation does not switch the cable off. The manufacturer states that the kit continues producing output regardless of ambient or pipe temperature.
If on/off control is required, the submittal specifies a field-installed Raychem AMC-F5 ambient thermostat. Follow the installation manual supplied with the FG2-6L kit. The minimum installation temperature is an installation limit, not a stated minimum operating temperature.
Technical Documents
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.