Lawler 71762-11 66-50 Thermostatic Mixing Valves
Lawler 71762-11 66-50 Thermostatic Mixing Valves - Rough Bronze is backordered and will ship as soon as it is back in stock.
Lawler 71762-11 Model 66® Master Mixing Valve
The Lawler 71762-11 Model 66® Master Mixing Valve is designed for high-capacity commercial and institutional applications requiring controlled mixing of hot and cold water.
The Model 66® incorporates Lawler’s Three-Way Protection™ and is intended to help maintain mixed-water temperature during changes or failures involving the thermostat, hot-water supply, or cold-water supply.
Key Features
- High-capacity master mixing valve for larger plumbing systems.
- Incorporates Lawler’s Three-Way Protection™.
- Three-Way Protection™ is intended to provide protection if the thermostat, hot-water supply, or cold-water supply fails.
- Source states outlet-water temperature control within ±3°F.
- Source states the Model 66® meets and exceeds the ASSE 1017 standard.
- Designed for commercial, industrial, and institutional water systems.
Applications
- Hospitals and medical centers.
- Schools and universities.
- Hotels and resorts.
- Correctional facilities.
- Industrial plants.
- Large commercial buildings.
Specifications
| Series | 66 |
|---|---|
| Model | 66-50 |
| Configuration | Standard |
| Application | Master Controller |
| Certifications | ASSE 1017, CSA B125.3, Lead Free |
| Connection Type | NPT |
| Inlet Connection Size | 3/4" |
| Outlet Connection Size | 1" |
| Minimum Flow | 7-1/2 GPM |
| Minimum Flow with Recirculation | 1/2 GPM |
| Rated Flow at 10 PSI | 25 GPM |
| Rated Flow at 45 PSI | 50 GPM |
| Temperature Ranges |
100°F – 150°F 50°F – 100°F 85°F – 135°F |
| Weight | 17 lbs |
| Part Numbers |
Rough Bronze: 71762-11 Rough Chrome: 71762-41 Polished Chrome: 71762-41-P |
Documents & Guides
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.