Lawler 84011 6125 Thermostatic Water Controller
Exposed mixing valve shall be of the thermostatic type with liquid-filled motor. In the event of interruption of hot or cold water supply or thermostat failure, the valve shall be designed to restrict flow by use of a sliding piston control mechanism with reverse seat closure. The valve shall maintain output temperature for changes in inlet pressures or temperature. Valve construction shall have lead free brass body and stainless steel piston and liner.
Specifications:
Series: 61 |
Model: 6125 |
Configuration: Thermostatic Water Controller |
Engineering Number: 84011 |
Certification/s: ASSE 1017, CSA B125.3 |
Connection Type: NPT |
Inlet Connection Size: 3/4" |
Outlet Connection Size: 3/4" |
Min Flow: 1 GPM |
Min Flow with Recirculation: 1/4 GPM" |
Rated Flow at 10 PSI: 10 GPM |
Rated Flow at 45 PSI: 25 GPM |
Temperature Range: 100°F – 150°F, 50°F – 100°F, 85°F – 135°F |
Finish: Polished Chrome, Rough Brass |
Part Number: 84011-09 Rough Bronze, 84011-10 Polished Chrome |